Mounting
The ADT-UZC-256 plugs into the ICA-4L in Unimode 2020/1010 systems, or mounts behind
modules in the Unimode 4-16 and Unimode II.
Additional Reference
The ADT-UZC-256 Zone Coder can be used with the Unimode 4-16, the Unimode II, and the
Unimode 2020/1010 Fire Alarm Control Panels. For more information on these systems,
refer to the following documents:
The Unimode 4-16 Installation & Programming Manual, Document A15019
The Unimode II Installation Manual, Document A15583
The Unimode 2020/1010 Manual, Document 51167
Standby Battery Calculation
Use the following figures when calculating the required standby battery capacity as indicated
in the above-mentioned installation manuals:
Standby Load: 35mA
Alarm Load: 85mA